Ethernet Option Board Function Guide
Section 9-1
9-1-2
Connecting the CX-Programmer to PLCs Online via Ethernet
Connecting within the
Same Segment
Use the UDP/IP version of the FINS communications service (i.e.,
FINS/UDP). FINS/UDP is supported by many OMRON products and is com-
patible with earlier Ethernet Units (CS1W-ETN01/ETN11/ETN21 and CJ1W-
ETN11/ETN21). The CX-Programmer can be connected and used with
FINS/UDP.
Connecting through
Multiple Segments
Use the TCP/IP version of the FINS communications service (i.e., FINS/TCP).
It provides automatic recovery at the TCP/IP layer from communications
errors (such as packet loss) that occur during multilevel routing. For CX-Pro-
grammer, FINS/TCP can be used to directly connect to the PLC online.
Using Media with
Unreliable Connections,
Such as a Wireless LAN
Use the TCP/IP version of the FINS communications service (i.e., FINS/TCP).
It provides automatic recovery at the TCP/IP layer from communications
errors (such as packet loss) resulting from unreliable connections. For CX-
Programmer, FINS/TCP can be used to directly connect to the PLC online.
Connecting from a
Personal Computer with a
Dynamic Private IP
Address
Depending on whether or not the connection will be within the same segment,
either use an IP address conversion method for dynamic IP addresses in the
UDP/IP version of the FINS communications service or use the TCP/IP ver-
sion of the FINS communications service.
It is possible to connect online to a PLC using the CX-Programmer from a
computer serving as a temporarily connected node or a permanent DHCP cli-
ent.
For CX-Programmer, FINS/TCP can be used to directly connect to the PLC
online.
Connecting through multiple segments, such as over the Internet:
Use FINS/TCP.
FINS
Internet
IP router
Firewall
Intranet
(Office floor)
CX-Programmer
FINS
Ethernet
Ethernet
Router
(Production line)
Ethernet
Connecting within the same segment:
Use FINS/UDP.
PLC
PLC
Wireless
FINS
Using media with unreliable
connections, such as wireless
LAN: Use FINS/TCP.
FINS
Connecting from a computer with a dynamic private IP address:
Use FINS/TCP or FINS/UDP.
CX-Programmer
CX-Programmer
Ethernet Option Board
Ethernet Option Board
CX-Programmer
Router
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...