![background image](http://html1.mh-extra.com/html/omron/cp1l-cpu-unit-03-2009/cp1l-cpu-unit-03-2009_operation-manual_742084277.webp)
243
Pulse Outputs
Section 5-2
SET PULSES: PULS(886)
PULS(886) is used to set the pulse output amount (number of output pulses)
for pulse outputs that are started later in the program using SPED(885) or
ACC(888) in independent mode.
SPEED OUTPUT:
SPED(885)
SPED(885) can be used to perform pulse output without acceleration or
deceleration. Either independent mode positioning or continuous mode speed
control is possible. For independent mode positioning, the number of pulses is
set using PULS(886).
SPED(885) can also be executed during pulse output to change the output
frequency, creating stepwise changes in the speed.
Operand
Contents
P
Port specifier
0000 hex: Pulse output 0
0001 hex: Pulse output 1
T
Pulse type
0000 hex: Relative pulse output
0001 hex: Absolute pulse output
N
First number
of pulses word
N and N+1 contain the number of pulses setting. (N contains
the rightmost 4 digits and N+1 contains the leftmost 4 digits.)
Relative pulse output:
0000 0000 to 7FFF FFFF hex (0 to 2,147,483,647)
Absolute pulse output:
8000 0000 to 7FFF FFFF hex (-2,147,483,648 to
2,147,483,647)
PULS(886)
P
T
N
P:
Port specifier
T:
Pulse type
N:
Number of pulses
Operand
Contents
P
Port specifier
0000 hex: Pulse output 0
0001 hex: Pulse output 1
T
Output
mode
Bits 0 to 3
Mode
0 hex: Continuous
1 hex: Independent
Bits 4 to 7
Direction
0 hex: CW
1 hex: CCW
Bits 8 to 11
Pulse output method (See note.)
0 hex: CW/CCW
1 hex: Pulse + direction
Bits 12 to 15 Not used. (Always 0 hex.)
F
First pulse frequency
word
F and F+1 contain the pulse frequency setting, in units of
1 Hz. (F contains the rightmost 4 digits and F+1 contains
the leftmost 4 digits.)
0000 0000 to 000186A0 hex (0 Hz to 100 kHz)
SPED(885)
P
T
F
P:
Port specifier
T:
Output mode
F:
First pulse frequency word
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...