420
Connecting Expansion Units and Expansion I/O Units
Section 7-1
7-1
Connecting Expansion Units and Expansion I/O Units
CP-series and CPM1A-series Expansion Units and Expansion I/O Units can
be connected to the CP1L. Up to three Expansion Units or Expansion I/O
Units can be connected to a CPU Unit with 30, 40 or 60 I/O points and one
Expansion Unit or Expansion I/O Unit can be connected to a CPU Unit with 20
or 14 I/O points.
The functionality and performance of CP-series Expansion Units and Expan-
sion I/O Units is the same as the functionality and performance of CP1MA-
series Expansion Units and Expansion I/O Units. CP-series Units are black,
and CPM1A-series Units are ivory.
Number of I/O Words
Note
CP1W-32ER/32ET/32ET1’s maximum number of simultaneously ON points is
24 (75%).
Unit name
Model
Current
consumption (mA)
I/O words
5 VDC
24 VDC
Input
Output
Expansion
Units
Analog Input Unit
CP1W-AD041
CPM1A-AD041
100
90
4
2
Analog Output Unit
CP1W-DA041
CPM1A-DA041
80
124
---
4
Analog I/O Unit
CPM1A-MAD01
66
66
2
1
CP1W-MAD11
CPM1A-MAD11
83
110
Temperature Control Unit
CP1W-TS001
CPM1A-TS001
40
59
2
---
CP1W-TS101
CPM1A-TS101
54
73
CP1W-TS002
CPM1A-TS002
40
59
4
---
CP1W-TS102
CPM1A-TS102
54
73
CompoBus/S I/O Link Unit
CP1W-SRT21
CPM1A-SRT21
29
---
1
1
DeviceNet I/O Link Unit
CPM1A-DRT21
48
---
2
2
Expansion
I/O Units
40-point I/O Unit
CP1W-40EDR
CPM1A-40EDR
80
90
2
2
CP1W-40EDT
CPM1A-40EDT
160
---
CP1W-40EDT1
CPM1A-40EDT1
160
---
32-point Output Unit
CP1W-32ER
49
131
---
4
CP1W-32ET
113
---
CP1W-32ET1
113
---
20-point I/O Unit
CP1W-20EDR1
CPM1A-20EDR1
103
44
1
1
CP1W-20EDT
CPM1A-20EDT
130
---
CP1W-20EDT1
CPM1A-20EDT1
130
---
16-point Output Unit
CP1W-16ER
CPM1A-16ER
42
90
---
2
CP1W-16ET
76
---
CP1W-16ET1
76
---
8-point Input Unit
CP1W-8ED
CPM1A-8ED
18
---
1
---
8-point Output Unit
CP1W-8ER
CPM1A-8ER
26
44
---
1
CP1W-8ET
CPM1A-8ET
75
---
CP1W-8ET1
CPM1A-8ET1
75
---
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...