22
System Configuration
Section 1-2
CPU Units with 14 or 20 I/O Points and AC Power (CP1L-L
@@
DR-A and
CP1L-L
@@
DT
@-A
)
When CP1W or CPM1A Expansion Units or Expansion I/O Units are con-
nected to a CPU Unit with 14 or 20 I/O Points and AC Power (CP1L-L
@@
DR-
A and CP1L-L
@@
DT-A), the external power supply cannot be used. If no
Expansion Units or Expansion I/O Units are connected, up to 200 mA can be
used.
CPU Units with DC Power
CPU Units with DC power do not have an external power supply.
■
Restrictions on the number of simultaneously ON output points
CP1W-32ER/32ET/32ET1’s maximum number of simultaneously ON points is
24 (75%).
■
Restrictions Imposed by Ambient Temperature
There are restrictions in the power supply voltage and output load current
imposed by the ambient temperature for CPU Units with DC power. Use the
CPU Unit within the following ranges of power supply voltage and output load
current.
CPU Units with Relay Outputs (CP1L-
@@@
DR-D)
Relay Output Load Current Derating Curves for CPU Units and Expansion I/O
Units
Note
The above restrictions, apply to the relay output load current from the CPU
Unit even if Expansion I/O Units are not connected.
CP1L-L14DR-D
CP1L-L20DR-D
CP1L-M30DR-D
CP1L-M40DR-D
CP1L-M60DR-D
50%
100%
55
°
C
40 45
Power voltage:
20.4 VDC
Power voltage:
21.6 VDC
0%
Ambient temperature
50%
100%
55
°
C
45
35
0%
Power voltage:
21.6 VDC
Power voltage:
20.4 VDC
Ambient temperature
50%
100%
55
°
C
45
35
0%
50
Power
voltage:
21.6 VDC
Power
voltage:
20.4 VDC
Ambient temperature
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...