706
Auxiliary Area Allocations by Address
Appendix D
A744 to
A746
All
Power ON
Clock Data 9
These words contain the time at
which the power was turned ON nine
times before the startup time stored
in words A510 to A511.
A744.00 to A744.07: Seconds (00 to
59)
A744.08 to A744.15: Minutes (00 to
59)
A745.00 to A745.07: Hour (00 to 23)
A745.08 to A745.15: Day of month
(00 to 31)
A746.00 to A746.07: Month (01 to
12)
A746.08 to A746.15: Year (00 to 99)
See at left.
Retained
Retained
Written
when
power is
turned
ON.
A747 to
A749
All
Power ON
Clock Data
10
These words contain the time at
which the power was turned ON ten
times before the startup time stored
in words A510 to A511.
A747.00 to A747.07: Seconds (00 to
59)
A747.08 to A747.15: Minutes (00 to
59)
A748.00 to A748.07: Hour (00 to 23)
A748.08 to A748.15: Day of month
(00 to 31)
A749.00 to A749.07: Month (01 to
12)
A749.08 to A749.15: Year (00 to 99)
See at left.
Retained
Retained
Written
when
power is
turned
ON.
A751
A751.11 DM Initial
Values Read
Error Flag
ON when an error occurred in trans-
ferring DM initial values from the DM
initial value area in flash memory to
the DM Area.
OFF: Normal
ON: Error
(failed to load)
Retained
Cleared
---
---
A751.12 DM Initial
Values Save
Execution
Error Flag
ON when the DM Initial Values
Transfer Password (A752) is incor-
rect or when the DM Initial values
area was not specified when starting
to transfer DM initial values from the
DM Area to the DM initial value area
in flash memory.
OFF: Normal
ON: Error
(failed to save)
Retained
Cleared
---
---
A751.13 DM Initial
Values Save
Error Flag
ON when an error occurred in trans-
ferring DM initial values from the DM
Area to the DM initial value area in
flash memory.
OFF: Normal
ON: Error
(failed to save)
Retained
Cleared
---
---
A751.14 DM Initial
Values Save
Flag
ON while DM initial values are being
transferred from the DM Area to the
DM initial value area in flash mem-
ory.
OFF when the transfer has been
completed.
OFF: Not being
saved
ON: Being
saved
Retained
Cleared
---
---
A751.15 DM Initial
Values Save
Start Bit
Turn ON this bit to start transferring
DM initial values. This bit is valid only
when a correct password is stored in
A752 and the DM Area Initial Value
Area is specified (i.e., when A753.00
is ON).
The system will turn this bit OFF
automatically when the transfer has
been completed.
Turned ON:
Transfer
started
OFF: Not trans-
ferring
ON: Transfer-
ring
Retained
Cleared
---
---
A752
All
DM Initial
Values Save
Password
Set the passwords here to transfer
DM initial values between the DM
area and the DM initial value area in
flash memory. The transfer will not
be started unless the correct pass-
word is set.
The transfer is started when A751.15
is turned ON.
The password will be cleared by the
system when the transfer has been
completed.
A5A5 hex:
Save initial val-
ues from DM to
flash
Retained
Cleared
---
---
A753
All
DM Initial
Values Save
Area Speci-
fication
Specifies the area to be transferred
to flash memory.
0001 hex: DM
Area specified
Retained
Cleared
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...