610
Troubleshooting
Section 11-2
Memory Errors
■
Reference Information
Probable cause
Possible remedy
Automatic transfer from the Memory Cassette
at startup failed because the required data is
not on the Memory Cassette.
Store the required data on the Memory Cas-
sette.
An error has occurred in memory. One or
more bits in A403 will turn ON to indicate
where the error has occurred. See below for
details.
• Memory Error Location
See below.
A403.00 is ON
A checksum error
has occurred in the
user program.
The power supply
was turned OFF
when backing up the
user program to
flash memory.
Transfer the user program again.
A403.04 is ON
A checksum error
has occurred in the
PLC Setup.
Transfer the PLC Setup again.
A403.07 is ON
A checksum error
has occurred in the
routing tables.
Transfer the routing tables again.
A403.09 is ON
The contents of a
Memory Cassette
could not be nor-
mally read to the
CPU Unit when
power was turned
ON.
Check to see if the files required for automatic
transfer at startup are present on the Memory
Cassette.
A403.10 is ON
There is a problem
with flash memory.
A hardware error has occurred in the CPU Unit.
Replace the CPU Unit.
Error flag
Memory Error Flag, A401.15
Error code (A400)
80F1
Error information
Memory Error Location, A403
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...