![background image](http://html1.mh-extra.com/html/omron/cp1l-cpu-unit-03-2009/cp1l-cpu-unit-03-2009_operation-manual_742084513.webp)
479
CompoBus/S I/O Link Units
Section 7-6
Operating Procedure
Connecting the
CompoBus/S I/O Link Unit
CompoBus/S I/O Link Units are connected to the CP1L CPU Unit. For CP1L
M-type CPU Units, up to three Units can be connected, including any other
Expansion Units and Expansion I/O Units that are also connected. The Units
can be connected in any order from the CPU Unit.
I/O Allocation
I/O words are allocated to the CompoBus/S I/O Link Unit in the same way as
to other Expansion Units and Expansion I/O Units, i.e., the next available input
and output words are allocated. As shown below, when “m” is the last allo-
cated input word and “n” is the last allocated output word, the CompoBus/S I/
O Link Unit is allocated “m+1” as its input word and “n+1” as its output word.
In the following example, a CompoBus/S I/O Link Unit is connected as the first
Unit after the CP1L CPU Unit.
Connect the Unit.
Determine the node
address of the
CompoBus/S I/O Link Unit
and set the DIP switch.
Wire the CompoBus/S
transmission path.
•
Connect the CompoBus/S I/O Link Unit.
•
The node number should be a unique number between
0 and 15.
•
Use the DIP switch to set the CompoBus/S I/O Link
Unit fs node number, communications mode, and the
status of output data when a communications error
occurs.
•
Connect the CompoBus/S I/O Link Unit to a
CompoBus/S transmission path.
BD L NC( BS-) N C
BD H
NC( BS+)
S
COMM
ERR
ON
1 2
3
4 5
6
No.
SRT21
EXP
SYSMAC
CP1L
L1
L2/N
COM
01
03
05
07
09
11
01
03
05
07
09
11
00
02
04
06
08
10
00
02
04
06
08
10
00
01
02
03
04
06
00
01
03
04
06
COM
COM
COM
COM
05
07
COM
02
COM
05
07
IN
OUT
CP1L M-type CPU Unit
CompoBus/S I/O Link Unit
Word m+1
CompoBus/S I/O Link Unit
8 inputs
8 outputs
Word n+1
CP1L
CPU Unit
CompoBus/S
I/O LInk Unit
Input words
Output words
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 102
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...