459
Analog I/O Units
Section 7-4
Creating a Ladder
Program
I/O Allocation
Two input words and one output word are allocated to the Analog I/O Unit
starting from the next word following the last allocated word on the CPU Unit
or previous Expansion Unit or Expansion I/O Unit.
Writing the Range Code
Write the range code to word n+1. A/D or D/A conversion begins when the
range code is transferred from the CPU Unit to the Analog I/O Unit. There are
five range codes, 000 to 100, that combine the analog input 1 and 2 and ana-
log output signal ranges, as shown below.
Example
The following instructions set analog input 0 to 4 to 20 mA, analog input 1 to 0
to 10 V, and the analog output to
−
10 to 10 V.
• The Analog I/O Unit will not start converting analog I/O values until the
range code has been written. Until conversion starts, inputs will be 0000,
and 0 V or 0 mA will be output.
• After the range code has been set, 0 V or 0 mA will be output for the 0 to
10-V,
−
10 to 10-V, or 0 to 20-mA ranges, and 1 V or 4 mA will be output for
the 1 to 5-V and 4 to 20-mA ranges until a convertible value has been
written to the output word.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
Range
code
Analog input 0 signal
range
Analog input 1 signal
range
Analog output signal
range
000
−
10 to 10 V
−
10 to 10 V
−
10 to 10 V
001
0 to 10 V
0 to 10 V
0 to 10 V
010
1 to 5 V/4 to 20 mA
1 to 5 V/4 to 20 mA
1 to 5 V
011
0 to 5 V/0 to 20 mA
0 to 5 V/0 to 20 mA
0 to 20 mA
100
---
---
4 to 20 mA
Analog I/O Unit
Word m+1
Word m+2
32 inputs
16 outputs
Word n+1
n+1
15
1 0 0
0
0
0
0
8 7 6 5
4
3
2
1
0
Analog
output
Analog
input 1
Analog
input 0
MOV(021)
#800A
n+1
First Cycle Flag
A200.11
Analog input 0: 4 to 20 mA
Analog input 1: 0 to 10 V
Analog output:
−
10 to 10 V
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...