45
Specifications
Section 2-2
Note
(1) The above values are for a cold start at room temperature for an AC pow-
er supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteris-
tics) is used in the inrush current control circuitry for the AC power sup-
ply. The thermistor will not be sufficiently cooled if the ambient
temperature is high or if a hot start is performed when the power sup-
ply has been OFF for only a short time, so in those cases the inrush
current values may be higher (as much as two times higher) than those
shown above.
• A capacitor delay circuit is used in the inrush current control circuitry
for the DC power supply. The capacitor will not be charged if a hot start
is performed when the power supply has been OFF for only a short
time, so in those cases the inrush current values may be higher (as
much as two times higher) than those shown above.
Always allow for this when selecting fuses and breakers for external cir-
cuits.
(2) Use the external power supply to power input devices. Do not use it to
drive output devices.
(3) This is the rated value for the maximum system configuration. Use the fol-
lowing formula to calculate DC power consumption for CPU Units with DC
power.
Formula:
DC-powered CP1L power consumption = 5-V current consumption
×
5 V/
70% (CP1L internal power efficiency) + 24-V current consumption
×
1.1
(current fluctuation factor)
Calculation Example
CP1L Power Consumption
= (0.47 A
×
5 V/70% + 0.263 A
×
24 V)
×
1.1
= 10.64 W
The above calculation results show that a power supply with a capacity of
7 W or greater is required.
System
CPU Unit
Expansion Unit or Expansion I/O Unit
Total
1st Unit
2nd Unit
3rd Unit
CP1L-M40DR-D
CP1W-20EDT
CP1W-TS001
CP1W-DA041
5 V
0.220 A
0.130 A
0.040 A
0.080 A
0.470 A
24 V
0.080 A
0.000 A
0.059 A
0.124 A
0.263 A
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...