84
CPU Unit Operation
Section 2-4
If high-speed response is required from input to output, execute IORF(097)
before and after the relevant instructions.
Note
IORF(097) has a relatively long execution time which increases with the num-
ber of words being refreshed. Be sure to consider the affect of this time on the
overall cycle time. Refer to the
CP Series Programmable Controllers Program-
ming Manual
for instruction execution times.
2-4-4
Initialization at Startup
The following initializing processes will be performed once each time the
power is turned ON.
• Confirm mounted Units and I/O allocations.
• Clear the non-holding areas of I/O memory according to the status of the
IOM Hold Bit. (See note 1.)
• Clear forced status according to the status of the Forced Status Hold Bit.
(See note 2.)
• Automatically transfer data from the Memory Cassette if one is mounted
and automatic transfer at startup is specified.
• Perform self-diagnosis (user memory check).
• Restore the user program. (See note 3.)
Note
(1) The I/O memory is held or cleared according to the status of the IOM Host
Bit and the setting for IOM Hold Bit Status at Startup in the PLC Setup
(read only when power is turned ON).
Note
When the mode is changed between PROGRAMMING mode and
RUN or MONITOR mode, I/O memory initialization is according to
the status of the IOM Hold Bit at that time.
(2) The forced status held or cleared according to the status of the Force Sta-
tus Hold Bit and the setting for Forced Status Hold Bit Status at Startup
in the PLC Setup (read only when power is turned ON).
IORF
St
E
IORF
2
5
Example
St
: Starting word
E
: End word
All the words from St to E, inclusive
are refreshed.
Here, the four words from CIO 2
to CIO 5 are refreshed.
Auxiliary bit
PLC Setup setting
IOM Hold Bit (A500.12)
Clear (OFF)
Hold (ON)
IOM Hold Bit Status
at Startup
Clear
(OFF)
At power ON: Clear
At mode change: Clear
At power ON: Clear
At mode change: Hold
Hold
(ON)
At power ON: Hold
At mode change: Hold
Auxiliary bit
PLC Setup setting
Forced Status Hold Bit (A500.13)
Clear (OFF)
Hold (ON)
Forced Status Hold
Bit Status at Startup
Clear
(OFF)
At power ON: Clear
At mode change: Clear
At power ON: Clear
At mode change: Hold
Hold
(ON)
At power ON: Hold
At mode change: Hold
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...