106
Mounting
Section 3-3
Mounting Height
The mounting height is approximately 90 mm.
When a cable is connected to an Option Board, however, the additional height
must be factored in. Always allow for the additional height when considering
the depth of the control panel in which the PLC is to be mounted.
3-3-2
Connecting Expansion Units and Expansion I/O Units
Leave approximately 10 mm of space between the CPU Unit and the Expan-
sion Units or Expansion I/O Units.
Mounting Method
CP1L-L14D
@
-
@
86
76
CP1L-L10D
@
-
@
66
56
Model
W1
W2
10 mm
CP1L CPU Unit
Expansion I/O Units or Expansion Units
100 mm
A
A
CP1L CPU Unit
with 30, 40 or 60 I/O
points
Expansion I/O Unit
with 32 or 40 I/O points
8 mm
100 mm
CP1L CPU Unit
with 10, 14 or 20 I/O
points
Expansion I/O Unit
with 8, 16 or 20 I/O points
Expansion Unit
8 mm
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...