157
Timers and Counters
Section 4-9
The following table shows when timers will be reset or maintained.
Note
1.
If the IOM Hold Bit (A500.12) is ON, the PV and Completion Flag will be
retained when a fatal error occurs (including execution of FALS instruc-
tions) or the operating mode is changed from PROGRAM mode to RUN or
MONITOR mode or vice-versa. The PV and Completion Flag will be
cleared when power is cycled.
2.
If the IOM Hold Bit (A50012) is ON and the PLC Setup’s
IOM Hold Bit Sta-
tus at Startup
setting is set to protect the IOM Hold Bit, the PV and Com-
pletion Flag will be retained when the PLC’s power is cycled.
3.
Since the TIML(542), TIMLX(553), MTIM(543), and MTIMX(554) instruc-
tions do not use timer numbers, they are reset under different conditions.
Refer to the descriptions of these instructions for details.
4.
The present value of TIM, TIMX(550), TIMH(015), TIMHX(551), TM-
HH(540), TMHHX(552), TIMW(813), TIMWX(816), TMHW(815) and TMH-
WX(817) timers programmed with timer numbers 0000 to 2047 will be
updated even when jumped between JMP and JME instructions or when
in a task that is on standby. The present value of timers programmed with
timer numbers 2048 to 4095 will be held when jumped or when in a task
that is on standby.
Forcing Bit Status
Timer Completion Flags can be force-set and force-reset.
Timer PVs cannot be force-set or force-reset, although the PVs can be
refreshed indirectly by force-setting/resetting the Completion Flag.
Restrictions
There are no restrictions in the order of using timer numbers or in the number
of N.C. or N.O. conditions that can be programmed. Timer PVs can be read as
word data and used in programming.
4-9-2
Counter Area (C)
The 4,096 counter numbers (C0000 to C4095) are shared by the CNT,
CNTX(546), CNTR(012), CNTRX(548), CNTW(814), and CNTWX(818)
instructions. Counter Completion Flags and present values (PVs) for these
instructions are accessed with the counter numbers.
When a counter number is used in an operand that requires bit data, the
counter number accesses the Completion Flag of the counter. When a
counter number is used in an operand that requires word data, the counter
number accesses the PV of the counter.
Instruction name
Effect on PV and Completion Flag
Operation in
Jumps and Interlocks
Mode change
1
PLC start-up
2
CNR(545)/CN
RX(547)
Jumps
(JMP-JME) or
Tasks on
standby
4
Interlocks
(IL-ILC)
TIMER: TIM/TIMX(550)
PV
→
0
Flag
→
OFF
PV
→
0
Flag
→
OFF
PV
→
9999
Flag
→
OFF
PVs refreshed in
operating timers
PV
→
SV
(Reset to SV.)
Flag
→
OFF
HIGH-SPEED TIMER:
TIMH(015)/TIMHX(551)
ONE-MS TIMER:
TMHH(540)/TMHHX(552)
ACCUMULATIVE TIMER:
TTIM(087)/TTIMX(555)
PV Maintained
PV Maintained
TIMER WAIT:
TIMW(813)TIMWX(816)
PVs refreshed in
operating timers
---
HIGH-SPEED TIMER WAIT:
TMHW(815)/TMHWX(817)
---
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...