Inverter Positioning
Section 5-3
Refer to
7-3 Analog Output Units
for operating procedures for the Analog Out-
put Unit.
■
Calculation Example
Conditions
Inverter’s maximum output frequency: 60 Hz
Calculation
The stored analog output value is calculated as follows:
Stored analog
output value
Inverter frequency
command value (Hz)
Inverter's max. output frequency (Hz)
6,000
CP1L
Automatic
calculations
Inverter
frequency
command value
Auxiliary Area
A23/A33
6,000
Inverter maximum
output frequency (Hz)
Stored analog
output value
Analog output
Unit: 0.01 Hz
1
100
Converting values in A23/A33 to Hz.
Converted in ladder program
Stored analog
output value
60
6,000
1
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
Auxiliary Area
A23/A33
(Unit: 0.01 Hz)
100
1
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...