160
Data Memory Area (D)
Section 4-10
4-10 Data Memory Area (D)
CPU Units with 30, 40 or 60 I/O points: D0 to D32767
CPU Units with 10, 14 or 20 I/O points: D0 to D9999 and D32000 to D32767
This data area is used for general data storage and manipulation and is
accessible only by word.
Data in the DM Area is retained when the PLC’s power is cycled or the PLC’s
operating mode is changed from PROGRAM mode to RUN/MONITOR mode
or vice-versa.
Although bits in the DM Area cannot be accessed directly, the status of these
bits can be accessed with the BIT TEST instructions, TST(350) and
TSTN(351).
Forcing Bit Status
Bits in the DM Area cannot be force-set or force-reset.
Indirect Addressing
Words in the DM Area can be indirectly addressed in two ways: binary-mode
and BCD-mode.
Binary-mode Addressing (@D)
When a “@” character is input before a DM address, the content of that DM
word is treated as binary and the instruction will operate on the DM word at
that binary address. The entire DM Area (D0 to D32767) can be indirectly
addressed with hexadecimal values 0000 to 7FFF.
BCD-mode Addressing (
*
D)
When a “
*
” character is input before a DM address, the content of that DM
word is treated as BCD and the instruction will operate on the DM word at that
BCD address. Only part of the DM Area (D0 to D09999) can be indirectly
addressed with BCD values 0000 to 9999.
Note
(1) If an address between D10000 and D31999 is specified as an operand
for a CPU Unit with 10, 14 or 20 I/O Points, an illegal area access error
will occur.
D32200
D32000
D32399
D9999
D0
D32199
D32399
D32200
D32199
D32767
D32400
D0
D32767
D32400
D10000
D31999
CPU Unit with 30, 40 or 60 I/O Points
CPU Unit with 10, 14 or 20 I/O Points
DM Fixed Allocation
Words for Modbus-RTU
Easy Master
DM Fixed Allocation
Words for Modbus-RTU
Easy Master
Do not use.
@D100
D256
0100
▲
Address actually used.
*
D100
D100
0100
▲
Address actually used.
Summary of Contents for CP1L CPU UNIT - 03-2009
Page 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Page 2: ......
Page 4: ...iv...
Page 10: ...x...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 70: ...36 Function Blocks Section 1 5...
Page 584: ...550 Trouble Shooting Section 8 7...
Page 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 630: ...596 Sample Application Section 9 12...
Page 654: ...620 Troubleshooting Unit Errors Section 11 4...
Page 662: ...628 Replacing User serviceable Parts Section 12 2...
Page 668: ...634 Standard Models Appendix A...
Page 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Page 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Page 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Page 806: ...772 Index...
Page 808: ...774 Revision History...