15
A likely cause of an
inc. DS3
alarm at the near-end system is a
failure at the far-end system or a problem with the cabling/wiring
between systems.
Repair according to local procedures.
............................................................................................................................................................
16
From the System View on the near-end NE, click the
Alarm List
button and click
Refresh
.
Result:
The
inc. DS3
alarm is no longer present.
............................................................................................................................................................
17
Are there any alarms listed?
If...
Then...
Yes
Proceed to the appropriate procedure
to clear the alarm.
No
STOP! End of Procedure.
E
N D
O F
S
T E P S
..............................................................................................................................................................................
Procedure 5-25: Clear
″
inc. DS3
″
conditions/alarms
Trouble clearing procedures
....................................................................................................................................................................................................................................
5 - 7 8
Lucent Technologies
365-372-333 R2.1
Issue 4, June 2005