Locate the required slot and determine if a circuit pack is physically
present in the required slot.
............................................................................................................................................................
5
Is a circuit pack physically present in the required slot?
If...
Then...
Yes,
Replace the failed circuit pack in
the required slot. Refer to the
appropriate circuit pack
replacement procedure in
Chapter 6, “Supporting
procedures”
Proceed to
No,
Continue with
............................................................................................................................................................
6
Using office records, determine if the required slot should contain a
circuit pack.
............................................................................................................................................................
7
Do office records show that the required slot should contain a circuit
pack?
If...
Then...
Yes,
Obtain the missing circuit pack
and install it into the required
slot.
Refer to the appropriate circuit
pack installation procedure in the
Metropolis
®
DMXplore Access
Multiplexer User Operations
Guide, 365-372-332.
Procedure 5-6: Clear
″
CP removed or CP
failure
″
alarm
Trouble clearing procedures
....................................................................................................................................................................................................................................
5 - 2 4
Lucent Technologies
365-372-333 R2.1
Issue 4, June 2005