Procedure 5-6: Clear
″
CP removed or CP failure
″
alarm
....................................................................................................................................................................................................................................
Overview
This procedure is used to clear a
CP removed or CP failure
alarm
indicated by a lighted Critical (
CR/MJ
) or Minor (
MN/ABN
) LED on
the SYSCTL faceplate, and reported as critical or minor in the
WaveStar
®
CIT Alarm List.
Before you begin
Prior to performing this procedure:
1.
Refer to
and
in this chapter.
2.
Refer to
and
“Electrostatic discharge” (1-13)
in
Procedure
Complete the following steps to clear a
CP removed or CP
failure
alarm.
............................................................................................................................................................
1
From the WaveStar
®
CIT System View, click the
Alarm List
button
and locate the
CP removed or CP failure
alarm in the resulting
alarm list.
............................................................................................................................................................
2
Determine the alarm level(s) for the active
CP removed or CP
failure
alarm(s) (for example, CR or MN). Clear the alarms in order
of severity, CR (SA) and then MN (NSA).
Important! The
CP removed or CP failure
alarm is generally
either CR (SA) when the circuit pack is active (either working
and unprotected or the protection switch failed) or MN (NSA)
when the circuit pack is protected and the protection switch
operated normally.
............................................................................................................................................................
3
Refer to the Probable Cause column in the alarm list and note the
corresponding slot AID.
............................................................................................................................................................
4
Important! The
CP removed or CP failure
alarm is reported
when a circuit pack is removed from a slot and when a slot is
equipped with a circuit pack that has a failed power module.
Trouble clearing procedures
....................................................................................................................................................................................................................................
365-372-333 R2.1
Issue 4, June 2005
Lucent Technologies
5 - 2 3