Procedure 5-25: Clear
″
inc. DS3
″
conditions/alarms
....................................................................................................................................................................................................................................
Overview
This procedure is used to clear the following
inc. DS3
alarms:
•
inc. DS3 sig. out of frequency defect
•
inc. (from DSX) DS3 AIS
•
inc. (from DSX) DS3 LOF
•
inc. (from DSX) DS3 LOS
•
inc. (from DSX) DS3 sig. failed
Refer
and
Chapter 3, “Alarms, conditions, and
for the possible alarm levels for the different alarms.
Before you begin
Prior to performing this procedure:
1.
Refer to
and
in this chapter.
2.
Refer to
“Electrostatic discharge” (1-13)
in
Procedure
Complete the following steps to clear an
inc. DS3
alarm.
............................................................................................................................................................
1
From the WaveStar
®
CIT System View, click the
Alarm List
button
and locate the
inc. DS3
alarm in the resulting alarm list.
............................................................................................................................................................
2
Determine the alarm level(s) for the active
inc. DS3
alarm(s) (for
example, CR, MJ, or MN). Clear the alarms in order of severity, CR,
MJ, MN, and then Not Alarmed.
............................................................................................................................................................
3
Refer to the Probable Cause column in the alarm list, determine the
port affected, and note the corresponding AID.
............................................................................................................................................................
4
Are there other incoming signal alarms present?
If...
Then...
Yes
Proceed to the appropriate procedure
to clear those alarms and continue
with
Trouble clearing procedures
....................................................................................................................................................................................................................................
365-372-333 R2.1
Issue 4, June 2005
Lucent Technologies
5 - 7 5