Reference:
“Procedure 6-15: Clean optical fibers, dual LC
adapters and LC lightguide buildouts (LBOs)” (6-214)
............................................................................................................................................................
10
If the LBO receptacle is acceptable, replace the near-end and then the
far-end circuit pack.
Reference:
Documentation for the far-end system or if
Metropolis
®
DMXplore,
Combination circuit pack” (6-148)
............................................................................................................................................................
11
From the System View, click the
Alarm List
button and click
Refresh
.
............................................................................................................................................................
12
Is the
section DCC channel failed
alarm still present?
If...
Then...
Yes
Contact your next level of support.
No
STOP! End of Procedure.
E
N D
O F
S
T E P S
..............................................................................................................................................................................
Procedure 5-50: Clear
″
section DCC
channel failed
″
alarm
Trouble clearing procedures
....................................................................................................................................................................................................................................
5 - 1 4 4
Lucent Technologies
365-372-333 R2.1
Issue 4, June 2005