External Signal Exchange
93/121
Operating Manual dryve D1, ST-, DC-, EC/BLDC-Motor Control System - V2.4
Example
– read “Statusword”
CANopen
COB-ID
DLC
Byte0
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
601h
8h
40h
41h
60h
00h
00h
00h
00h
00h
Modbus TCP as Gateway
6060h Modes of Operation
Short description
Preselection of the operating mode
Parameter Name
Modes_of_operation
Object Type
VAR
0x7
Data Type
INTEGER8
0x0002
Access
RWW
Standard Value
1
PDO Mapping
Yes
Value assignment
0
No mode change / no mode assigned
1
Profile Position mode
2
Not implemented
3
Profile Velocity mode
4
Not implemented
5
reserved
6
homing mode
7
Not implemented
8
Cyclic Synchronous Position mode
Entries 9-128 not allocated
6061h Modes of Operation Display
Short description
Object for feedback of current operating mode
Parameter Name
Modes_of_operation_display
Object Type
VAR
0x7
Data Type
INTEGER8
0x0002
Access
RO
PDO Mapping
Yes
Value assignment
0
No mode change / no mode assigned
1
Profile Position mode
2
Not implemented
3
Profile Velocity mode
4
Not implemented
5
reserved
6
homing mode
7
Not implemented
8
Cyclic Synchronous Position mode
Entries 9-128 not allocated
6064h Position Actual Value
Short description
Indication of the current position of the position encoder
Parameter Name
Position_actual_value
Object Type
VAR
0x7
Data Type
INTEGER32
0x0004
Access
RO
PDO Mapping
Yes
0 - 4
5
6
7
8
9 - 11
12
13
14 - 17
18
19 - 22
bin
0000 0000
0000 1101 0000 0000
0010 1011 0000 1101 0000 0000
0110 0000
0100 0001
0000 0000
0000 0010
not send
hex 0h
0Dh
0h
2Bh
0Dh
0h
60h
41h
0h
2h
not send
dec 0
13
0
43
13
0
96
65
0
2
not send
Byte