Installation
16/121
Operating Manual dryve D1, ST-, DC-, EC/BLDC-Motor Control System - V2.4
Environmental Conditions
WARNING!
-
Danger of malfunction
-
Fire hazard
-
Explosion hazard
-
Danger of electric shock
Never operate the dryve D1 motor control system in water or in an aggressive, flammable or explosive atmosphere.
Ambient Temperature
Operation
-20 °C to +45 °C
Transport
-40 °C to +60 °C
Storage
-40 °C to +60 °C
Relative Humidity
≤ 90 %, non-condensing
Protection Class
IP 30
Degree of soiling according to EN 61010
1
MTTF value @ 25°C
64,72 Years
4 Installation
4.1 Mechanical Installation
-
Installation in a control cabinet by mounting it on a TS 35 supporting rail (EN 50022) or by removing the mounting clip
and screwing the base of the housing directly onto a mounting plate.
-
The device must be aligned vertically. For horizontal alignment, the maximum power must be reduced by 30% to
prevent overheating
-
The installation site must be free of extreme vibrations or shocks.
-
Minimum free space above and underneath the device: 50 mm
-
The ventilation openings are to be kept free
-
35 mm of space for plug-in connectors and cables must be kept free in front of the device.
-
If several dryve D1 devices are placed next to each other, a space of 10 mm must be kept in between (applies for
continuous operation)
-
If several dryve D1 devices are placed without space in between, the maximum continuous current must be reduced to
5.5 A or an active cooling system must be used (applies for continuous operation)
-
The heated air flow of other devices and components must not be led through the area of the dryve D1.