Installation
26/121
Operating Manual dryve D1, ST-, DC-, EC/BLDC-Motor Control System - V2.4
4.2.3 Communication Interfaces
X7 CANopen Port
The dryve D1 may be controlled with the CANopen communication protocol. For this purpose, the dryve D1 will be connected to
the bus and the master via the CANopen port. The standard pin assignment in accordance with CiA 301 is illustrated in the
table.
CAN Port Pin Assignment
Top view of CANopen port
Pin
Layout
Designation
X7.1
--------------
Not assigned
X7.2
CAN_L
CAN Signal Low
X7.3
CAN_GND
CAN ground
X7.4
--------------
Not assigned
X7.5
--------------
Not assigned
X7.6
--------------
Not assigned
X7.7
CAN_H
CAN Signal High
X7.8
--------------
Not assigned
X7.9
--------------
Not assigned
Transmission Speeds
Possible transmission speeds are dependent on the used cable lengths. The dryve D1 supports
up to 1 Mbit/s.
Baud Rate
Length
10kbit/s
6,700m
20kbit/s
3,300m
50kbit/s
1,000m
125kbit/s
500m
250kbit/s
250m
500kbit/s
125m
1Mbit/s
25m
Termination Resistors
At each end of the bus cable, the CAN bus needs a termination resistor with 120 Ω between the CAN high channel and the CAN
low channel. These resistors are needed for defined difference-signal evaluation of the CAN low and CAN high channels.
X8 Ethernet/Modbus TCP Gateway Port
The assignment of the X8 Ethernet port corresponds to the standard assignment according to TIA-568A/B.