Frequently Asked Questions
DECT
183
18.3
DECT
Note:
In the following explanations it is assumed that a U
pn
interface card has been installed (in an OpenCom 130 or an
OpenCom 150).
The LED of the RFP 22/24 base station is flashing, but none of the DECT de-
vices is functioning.
Make sure the terminal setting for the corresponding U
pn
port is set to
RFP 22/24
(
Configurator
,
PBX Configuration: Ports: U
pn
menu).
If multiple
RFP 22/24
base stations are installed, the blinking LED indicates that
synchronisation is not finished.
The LED of the RFP 22/24 is continuously lit up, but one of the cordless DECT
devices is indicating “No connection”.
You have not registered this DECT device. Configure a port in the
Configurator
and start the enrolment procedure (
PBX Configuration: Devices: DECT Phones
menu).
Is it possible to increase the time for the enrolment procedure?
You must manually enter the IPEI of the DECT device in the
Configurator
. The
enrolment time is then increased to one hour (
PBX Configuration: Devices: DECT
Phones
menu).
Another manufacturer’s DECT device is not functioning.
Check whether the DECT device supports the DECT GAP standard. In the
Configu-
rator
, also make sure
GAP
is set for this DECT device (
PBX Configuration:
Devices: DECT Phones
menu).
The startup procedure of the RFP 22/24 take a long time? What is the reason?
This behaviour may indicate a problem with the reference clock. Refer also to
What
are some of the causes for problems when sending and/or receiving faxes?
starting on
page 182.