Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
289
2.8.12.3 Overview of functions:
Code
Name
Page
PtC-
[PTC MANAGEMENT]
see "PTC MANAGEMENT (PtC-)" on page 289
rSt-
[FAULT RESET]
see "FAULT RESET (rSt-)" on page 289
Atr-
[Automatic restart]
see "AUTOMATIC RESTART (Atr-)" on page 290
FLr-
[CATCH ON THE FLY]
see "CATCH ON THE FLY (FLr-)" on page 290
tHt-
[MOTOR THERMAL PROT.]
see "THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
OPL-
[Output Phase Loss]
see "THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
IPL-
[Input phase loss]
see "LOSS LINE PHASE (IPL-) AND OVERTEMP. DRIVE (OHL-)" on page 294
OHL-
[DRIVE OVERHEAT]
see "LOSS LINE PHASE (IPL-) AND OVERTEMP. DRIVE (OHL-)" on page 294
SAt-
[THERMAL ALARM STOP]
see "Delayed stop at a thermal overload alarm" on page 296
EtF-
[External fault]
see "EXTERNAL FAULT (EtF-)" on page 296
USb-
[UnderV. fault mgt]
see "UNDERVOLTAGE MGT. (USb-)" on page 297
tIt-
[IGBT test]
see "MGT. UNDERVOLTAGE (USB-) AND IGBT TEST (TLT-)" on page 298
LFL-
[4-20 mA LOSS]
see "4-20 mA LOSS (LFL-)" on page 299
InH-
[Fault inhibit assign.]
see "INHIBIT FAULT (InH-)" on page 299
CLL-
[COMM FAULT MGT]
see "NETWORK FAULT MGT. (CLL-)" on page 300
Sdd-
[ENCODER FAULT]
see "ENCODER FAULT (Sdd-) and LIMIT. CURRENT - TORQUE. (tld-)" on page 301
tId-
[TORQUE/CURRENT LIM .]
see "ENCODER FAULT (Sdd-) and LIMIT. CURRENT - TORQUE. (tld-)" on page 301
dLd-
[DYNAMIC LOAD DETECT.]
see "DYNAMIC LOAD DETECT. (dLd-)" on page 303
brP-
[BRAKE RESIST PROTEC-
TION]
see "BRAKE RESIST PROTECTION (brP-) and AUTO-TUNE FAULT (tnF-)" on page 304
tnF-
[AUTO TUNING FAULT]
see "BRAKE RESIST PROTECTION (brP-) and AUTO-TUNE FAULT (tnF-)" on page 304
PPI-
[CARDS PAIRING]
see "Cards pairing" on page 306
LFF-
[FALLBACK SPEED]
see "FALLBACK SPEED (LFF-), FAST STOP (FSt-) and DC INJECT. (dCI)" on page 306
FSt-
[FAST STOP]
see "FALLBACK SPEED (LFF-), FAST STOP (FSt-) and DC INJECT. (dCI)" on page 306
dCI-
[DC Injection]
see "FALLBACK SPEED (LFF-), FAST STOP (FSt-) and DC INJECT. (dCI)" on page 306
The parameters of the menu
[FAULT MANAGEMENT]
(FLt-)
can only be changed in the stopped state without run
command. Parameters with an arrow symbol in the "Code column are exceptions to this rule. These parameters
can be changed during operation and in stop mode.
2.8.12.4 PTC sensor
The inverter can manage 3 sets of PTC probes in order to protect the motors:
•
One PTC probe on logic input LI6. Activation takes place via switch "
SW1
and
SW2
" on the control card.
Each of these sets of PTC sensors is monitored for the following faults:
•
Overtemperature on the motor
•
Sensor break fault
•
Sensor short-circuit fault
Protection via PTC probes does not disable protection via I
2
t calculation performed by the inverter. The two types
of protection can be combined.
[PTC MANAGEMENT] (PtC-)
Code
Name/Description
Factory settings
PtC-
[PTC MANAGEMENT]
PtCL
[LI6 = PTC probe]
[No]
(nO)
Access is possible when control card switch
SW1
and
SW2
is set to PTC.
nO
[No]
(nO)
: Not used.
AS
[Always]
(AS)
: PTC probe faults are monitored permanently, even if the power supply is not connected (as long as the control remains connected
to the power supply).
rdS
[Switch on]
(rdS)
: "PTC probe" faults are monitored while the inverter power supply is connected.
rS
[Motor on]
(rS)
: The PTC probes are monitored while the motor is switched on.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...