Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
167
The parameters in the menu
[INPUTS/OUTPUTS CFG]
(I-O-)
can only be changed if the inverter has been stopped
and no run command is present.
Input and Output Parameters
Code
Name/Description
Factory settings
tCC
[2/3 wire control]
[2 wire control]
(2C)
2C
[2 wire control]
(2C)
3C
[3 wire control]
(3C)
2 wire control: This is the input state (0 or 1) or edge (0 to 1 or 1 to 0), which controls running or stopping.
Example for wiring as "source":
Ll1: Forward
Llx: Reverse
3-wire control (edge-controlled): A "forward" or "reverse" pulse is sufficient for motor startup. A "stop" pulse is sufficient to stop the motor.
Example for wiring as "source":
Ll1: Stop
Ll2: Forward
Llx: Reverse
Warning!
ACCIDENTAL OPERATION OF DEVICE
To change the assignment of
[2/3 wire control]
(tCC)
, press down on ENT key for 2 s.
This resets the following functions to their default values:
Type 2 wire control]
(tCt)
and
[anti-clockwise operation]
(rrS)
below,
and all of the functions that assign the logic inputs and analog inputs.
The selected macro configuration will also be reset if they contain customer-specific settings (loss of user-specific settings).
It is recommended that this parameter be configured before the menus
[CONTROL]
(CtL-)
and
[APPLICATIONS-FCT.]
(FUn-)
.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
tCt
[2 wire type]
[Edge control]
(trn)
LEL
[Level]
(LEL)
: The status 0 or 1 is used for the run command (1) or the stop command (0).
trn
[Edge control]
(trn)
: A state change (edge or transition) is required to initiate operation and to prevent an inadvertent restart after power failure.
PFO
[Prio right]
(PFO)
: State 0 or 1 is taken into account for run or stop, but the "run forward" input takes priority over the "run reverse" input
rrS
[Reverse assign.]
[LI2]
(LI2)
nO
[No]
(nO)
: Not active
LI1
[LI1]
(LI1)
to
[LI6]
(LI6)
C101
[C101]
(C101)
to
[C115]
(C115)
: Not applicable
-
[C201]
(C201)
to
[C215]
(C215)
: With built-in communication interface in
[I/O profile]
(IO)
-
[C301]
(C301)
to
[C315]
(C315)
: With communication card in
[I/O profile]
(IO)
Cd00
[CD00]
(Cd00)
to
[CD13]
(Cd13)
: In
[I/O profile]
(IO)
the switchover is possible with logic inputs
-
[CD14]
(Cd14)
to
[CD15]
(Cd15)
: In
[I/O profile]
(IO)
the switchover is possible with logic inputs
Assignment of the reverse direction command.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...