Programming guidelines
168
ACOPOSinverter P84 User's Manual 2.10
[LI1] (L1-) and [LIx CONFIGURATION] (L--)
Code
Name/Description
Setting range
Factory settings
L1-
[LI1]
L1A
[Assign. LI1]
Read-only parameter, cannot be configured.
It displays all the functions that are assigned to input LI1 in order to check for multiple assignments.
L1d
[LI1 On Delay]
0 to 200 ms
0
This parameter is used to enable delayed consideration of the logic input's transition to state 1. This delay can be set to a value from 0 to 200 ms,
and it serves to filter possible interference. The change to state 0 is taken into account without delay.
Warning!
ACCIDENTAL OPERATION OF DEVICE
Make sure that the set delay poses no threat and no unintentional operation.
Depending on the deceleration values of the different logic inputs, the order of the acquisition of these inputs may change, leading
to an unexpected operation.
Failure to follow these instructions will result in death or serious injury.
L--
[LIx CONFIGURATION]
All available logic inputs of the inverter are processed as in the example LI1 above (up to LI6, LI10 or LI14, depending on whether the option
cards were used.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...