Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
155
Code
Name/Description
Setting range
Factory settings
U0
[U0]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter can be accessed when
[motor control type]
(Ctt)
=
[V/f Reg 2P]
(UF2)
or
[V/f Reg 5P]
(UF5)
.
U1
[U1]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
F1
[F1]
0 to 599 Hz
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
U2
[U2]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
F2
[F2]
0 to 599 Hz
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
U3
[U3]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
F3
[F3]
0 to 599 Hz
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
U4
[U4]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
F4
[F4]
0 to 599 Hz
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
U5
[U5]
0 to 599 depending on the size
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
F5
[F5]
0 to 599 Hz
0
Setting the V/f characteristic
The parameter is accessible when
[Motor control type]
(Ctt)
=
[V/f Reg 5P]
(UF5)
.
UFr
[IR compensation]
1)
25 to 200%
100%
This parameter can be accessed if
[motor control type]
(Ctt)
is not
[V/f Reg 2P]
(UF2)
and
[V/f Reg 5P]
(UF5)
.
Enables increase in the optimization of the torque at very low speed (
[IR-compens.]
(UFr)
if the torque is not sufficient).
Make sure that the value of
[IR compens.]
(UFr)
is not too high in relation to the heated motor (risk of instability).
SLP
[Slip compensation]
1)
0 to 300%
100%
This parameter can be accessed if
[motor control type]
(Ctt)
is not
[V/f Reg 2P]
(UF2)
and
[V/f Reg 5P]
(UF5)
.
Allows the adjustment of the rated motor speed by entering the set slip compensation.
The speeds given on motor nameplates are not necessarily exact.
•
If slip setting is < actual slip: The motor is not rotating at the correct speed in steady state, but at a speed lower than the reference.
•
If slip setting is > actual slip: The motor is overcompensated and the speed is unstable.
1)
This parameter can also be accessed via the
[SETTINGS]
(SEt-)
menu.
Code
Name/Description
Setting range
Factory settings
VC2
[Vector control 2pt]
[No]
(nO)
This parameter cannot be accessed if
[Motor control type]
(Ctt)
is not
[Sync. Motor.]
(SYn)
.
nO
[No]
(nO)
: Function not active.
YES
[Yes]
(YES)
: Function active.
Is used in applications in which the motor rated speed and frequency must be exceeded to optimize the operation for constant power, or if the
maximum voltage of the motor must be limited to a value below the line voltage.
The voltage/frequency profile must be adapted based on the capabilities of the motor for operating at maximum voltage (UCP) and maximum
frequency (FCP).
Motor voltage.
Maximum voltage UCP
Rated voltage UnS
Rated frequency FrS
Frequency
Maximum frequency FCP
UCP
[Volt. const. power]
According to in-
verter performance
In accordance with
the inverter power and
[Standard Motor Freq.]
(bFr)
The parameters can be activated if
[vector control 2pt]
(VC2)
=
[Yes]
(YES)
.
FCP
[Freq const power]
0 to 599 Hz
[Standard Motor freq.]
(bFr)
The parameters can be activated if
[vector control 2pt]
(VC2)
=
[Yes]
(YES)
.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...