Code
Name/Description
Setting range
Factory settings
bEt
[Brake engage time]
0 to 5.00 s
0 s
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Brake engage time (brake response time)
JdC
[Jump at reversal]
[Auto]
(AUtO)
0 to 10 Hz
[Auto]
(AUtO)
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
ttr
[Time to restart]
0.00 to 15.00 s
0 s
see "[BRAKE LOGIC CONTROL] (bLC-)" on page 223
Delay between the end of a brake engage sequence and the start of a brake release sequence
tLIM
[Motoring torque lim]
0 to 300%
100%
see "LIM. TORQUE (tOL-)" on page 258
.
Torque limiting for generator operation in percent or 0.1% of the rated torque in accordance with the parameter
[Torque limit. activ.]
(IntP)
.
tLIG
[Gen. torque lim]
0 to 300%
100%
see "LIM. TORQUE (tOL-)" on page 258
.
Torque limiting for generator operation in percent or 0.1% of the rated torque in accordance with the parameter
[Torque ref. assign.]
(IntP)
.
trH
[Traverse freq. high]
0 to 10 Hz
4 Hz
see "TRAVERSE CONTROL (trO-)" on page 282
trL
[Traverse freq. low]
0 to 10 Hz
4 Hz
see "TRAVERSE CONTROL (trO-)" on page 282
qSH
[Quick step High]
0 to
[Traverse HSP]
(trH)
0 Hz
see "TRAVERSE CONTROL (trO-)" on page 282
qSL
[Quick step Low]
0 to
[Traverse LSP]
(trL)
0 Hz
see "TRAVERSE CONTROL (trO-)" on page 282
Ctd
[Current threshold]
0 to 1.5 In
1)
In
1)
Current threshold value of the function
[thresh. I err.]
(CtA)
, that is assigned to a relay or a logic output,
see "R1 CONFIGURATION" on page 176
ttH
[High torque thd.]
-300 to 300%
100%
Upper torque threshold value of function
[high torque alarm]
(ttHA)
that is assigned to a relay or logic output,
.
ttL
[Low torque thd.]
-300 to 300%
50%
Lower torque threshold value of function
[Low torque alarm]
(ttLA)
that is assigned to a relay or logic output (
) as a percentage of the nominal torque
1)
In is the same as the rated current specified in the installation instructions or on the nameplate of the inverter.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can also be
accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed in these menus, on
the pages indicated, to aid programming.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...