Installation guide
ACOPOSinverter P84 User's Manual 2.10
35
1.3.4.1.3 8I84T200550.01P-1, 8I84T200750.01P-1, 8I84T201100.01P-1
Model number
8I84T200550.01P-1
8I84T200750.01P-1
8I84T201100.01P-1
General information
Certifications
CE
Yes
KC
Yes
UL
cULus E225616
Power conversion equipment
Motor power
Listed on nameplate, 1-phase
4 kW
5 PS
5.5 kW
7.5 PS
-
Listed on nameplate, 3-phase
5.5 kW
7.5 PS
7.5 kW
10 PS
11 kW
15 PS
Mains connection
Mains input voltage, 1-phase
1x 200 VAC -15% to 240 VAC +10%
1)
-
Mains input voltage, 3-phase
3x 200 VAC -15% to 240 VAC +10%
Frequency
50 to 60 Hz ±5%
Apparent power (at 240 VAC)
-
19 kVA
Apparent power (at 240 VAC), 1-phase
7 kVA
9.5 kVA
-
Apparent power (at 240 VAC), 3-phase
12.8 kVA
16.4 kVA
-
Max. assumed short circuit current (lsc)
(short circuit current at connection point)
-
22 kA
Max. assumed short circuit current (Isc)
(short circuit current at connection point), 1-phase
5 kA
-
Max. assumed short circuit current (Isc)
(short circuit current at connection point), 3-phase
22 kA
-
Max. mains current with optional mains choke
At 230 VAC
19.5 A
26.5 A
37.1 A
Mains current
At 200 VAC
-
53.3 A
At 200 VAC, 1-phase
34.9 A
2)
47.3 A
2)
-
At 200 VAC, 3-phase
35 A
3)
45 A
3)
-
At 240 VAC
-
45.8 A
At 240 VAC, 1-phase
29.9 A
2)
40.1 A
2)
-
At 240 VAC, 3-phase
30.8 A
3)
39.4 A
3)
-
Power dissipation at nominal load and nominal
clock frequency
293 W
363 W
566 W
Integrated EMC filter
Yes
4)
No
4)
Line-conducted and radiated emissions
With integrated filter
Motor cable length per IEC/EN 61800-3
Cat. C1 environment 1 (public power system)
-
Motor cable length per IEC/EN 61800-3
Cat. C2 environment 1 (public power system)
-
Motor cable length per IEC/EN 61800-3
Cat. C3 environment 2 (industrial power system)
≤10 m / ≤5 m
5)
-
With add-on filter
8I0FT026.300-1
8I0FT046.300-1
8I0FT072.300-1
With add-on filter
Motor cable length per IEC/EN 61800-3
Cat. C1 environment 1 (public power system)
≤50 m / ≤20 m
6)
≤50 m / ≤25 m
Motor cable length per IEC/EN 61800-3
Cat. C2 environment 1 (public power system)
≤100 m / ≤50 m
7)
≤100 m / ≤50 m
Motor cable length per IEC/EN 61800-3
Cat. C3 environment 2 (industrial power system)
≤100 m / ≤50 m
7)
≤100 m / ≤50 m
Motor connection
Derating of continuous output current depending on
ambient temperature
At nominal clock frequency (4 kHz or 2.5 kHz
with higher inverter power)
No derating (up to 50°C)
Other clock frequencies
The derating curves are included in the installation instructions, which
can be downloaded from the website (www.br-automation.com).
Derating of continuous output current depending on
installation elevation
Starting at 1000 m above sea level
1%, per 100 m
Max. continuous output current (In)
At 230 VAC, 1-phase
17.5 A
8)
27.5 A
8)
-
At 230 VAC, 3-phase
27.5 A
8)
33 A
8)
54 A
Max. transient current for 60 s, 1-phase
26.3 A
41.3 A
-
Max. transient current for 60 s, 3-phase
41.3 A
49.5 A
81 A
Max. transient current for 2 s, 1-phase
28.8 A
45.3 A
-
Max. transient current for 2 s, 3-phase
45.3 A
54.5 A
89.1 A
Output frequency range
0.5 to 599 Hz
Nominal clock frequency
4 kHz
Table 12: 8I84T200550.01P-1, 8I84T200750.01P-1, 8I84T201100.01P-1 - Technical data
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...