Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
263
2.8.11.21 Motor protection command
This allows the inverter to control a contactor located between the inverter and the motor. The request for the
contactor to close is made when a run command is sent. The request for the contactor to open is made when there
is no longer any current in the motor.
Caution!
If a DC injection braking function has been configured, it should not be left operating too long in stop
mode, as the contactor only opens at the end of braking.
Failure to follow this instruction can result in equipment damage.
2.8.11.21.1 Output contactor feedback
The corresponding logic input should be at 1 when there is no run command and at 0 during operation.
In the event of an inconsistency, the inverter trips on an
FCF2
fault if the output contactor fails to close (LIx at 1)
and on an
FCF1
fault if it is stuck (LIx at 0).
With the parameter
[Delay start Mot.cont.]
(dbS)
the triggering of the fault can be delayed in the case of a run
command and the parameter
[Time delay motor contact]
(dAS)
delays the fault in the even of a stop command.
Note:
The fault
FCF2
(the contactor does not close) can be switched on again by a change from 1 to 0 of the
run command (0 → 1 → 0 with a 3-wire control).
Control element
Response
d01/R2
Functions
[Out. contact.]
(OCC)
and
[Output contact. fdbk]
(rCA)
can be used individually or at the same time.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...