2.8.5.4 Macro configuration parameters
Assignment of the inputs / outputs
Input/Output
[Start/Stop]
[M. handling]
[Gen. Use]
[Hoisting]
[PID REGULA-
TOR]
[Network C.]
[Mast./Slave]
[AI1]
[Ref.1 channel]
[Ref.1 channel]
[Ref.1 channel]
[Ref.1 channel]
[Ref.1 channel]
(PID setpoint)
[Ref.2 channel]
([Ref.1 channel]
= Integrated bus
connection)
[Ref.1 channel]
[AI2]
[No]
[Summing ref. 2] [Summing ref. 2]
[No]
[PID feedback]
[No]
[Ref. Torq.]
[AO1]
[No]
[No]
[No]
[No]
[No]
[No]
[No]
[R1]
[No fault]
[No fault]
[No fault]
[No fault]
[No fault]
[No fault]
[No fault]
[R2]
[No]
[No]
[No]
[BRAKE LOGIC
CONTROL]
[No]
[No]
[No]
[LI1] (2-wire)
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
LI2 (2-wire)
[Reverse assign.] [Reverse assign.] [Reverse assign.]
[Reverse assign.] [Reverse assign.] [Reverse assign.] [Reverse assign.]
LI3 (2-wire)
[No]
[2 preset speeds] [Jog]
[Fault reset con-
figuration]
[PID integral re-
set]
[Ref
channel
switching]
[Alt Torque / v]
LI4 (2-wire)
[No]
[4 preset speeds] [Fault reset configu-
ration]
[External fault]
[Assign 2 PID ref.] [Fault reset con-
figuration]
[Fault reset con-
figuration]
LI5 (2-wire)
[No]
[8 preset speeds] [Torque limit. activ.]
[No]
[Assign 4 PID ref.] [No]
[No]
LI6 (2-wire)
[No]
[Fault reset con-
figuration]
[No]
[No]
[No]
[No]
[No]
[LI1] (3-wire)
Start enab.
Start enab.
Start enab.
Start enab.
Start enab.
Start enab.
Start enab.
LI2 (3-wire)
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
[Forward]
LI3 (3-wire)
[Reverse assign.] [Reverse assign.] [Reverse assign.]
[Reverse assign.] [Reverse assign.] [Reverse assign.] [Reverse assign.]
LI4 (3-wire)
[No]
[2 preset speeds] [Jog]
[Fault reset con-
figuration]
[PID integral re-
set]
[Ref. 2 switching] [Alt Torque / v]
LI5 (3-wire)
[No]
[4 preset speeds] [Fault reset configu-
ration]
[External fault]
[Assign 2 PID ref.] [Fault reset con-
figuration]
[Fault reset con-
figuration]
LI6 (3-wire)
[No]
[8 preset speeds] [Torque limit. activ.]
[No]
[Assign 4 PID ref.] [No]
[No]
Graphic display terminal keys
F1 key
[No]
[No]
[No]
[No]
[No]
Control via graph-
ic display terminal
[No]
Keys F2, F3, F4
[No]
[No]
[No]
[No]
[No]
[No]
[No]
In 3-wire control, the assignment of inputs LI1 to LI6 shifts.
Note:
These assignments are reinitialized every time the macro configuration changes.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...