4.3 Mains choke
4.3.1 Order data
Model number
Short description
Figure
ACOPOSinverter P74/P84 - Mains chokes
8I0CS025.000-1
Mains choke 1-phase 25 A, for ACOPOSinverter P84 1x 200 to
240 V, 3 kW
8I0CS045.000-1
Mains choke 1-phase 45 A, for ACOPOSinverter P84 1x 200 to
240 V, 4 to 5.5 kW
ACOPOSinverter P74/P76/P84 - Line chokes
8I0CT004.000-1
Mains choke 3-phase 4 A, for ACOPOSinverter P74 3x 380 to
500 V, 0.37 to 1.5 kW, for ACOPOSinverter P84 3x 200 to 240
V, 0.37 to 0.75 kW and 3x 380 to 480 V, 0.75 to 1.5 kW
8I0CT010.000-1
Mains choke 3-phase 10 A, for ACOPOSinverter P74 3x 380 to
500 V, 2.2 to 4 kW, for ACOPOSinverter P84 3x 200 to 240 V,
1.5 to 2.2 kW and 3x 380 to 480 V, 2.2 to 4 kW
8I0CT016.000-1
Mains choke, 3-phase 17 A, for ACOPOSinverter P74 3x 380 to
500 V, 5.5 to 7.5 kW, for ACOPOSinverter P84 3x 200 to 240 V,
3 kW and 3x 380 to 480 V, 5.5 to 7.5 kW
8I0CT030.000-1
Mains choke 3-phase 30 A, for ACOPOSinverter P74 3x 380 to
500 V, 11 to 15 kW, for ACOPOSinverter P84 3x 200 to 240 V,
4 to 5.5 kW and 3x 380 to 480 V, 11 to 15 kW
8I0CT060.000-1
Mains choke 3-phase 60 A, for ACOPOSinverter P84 3x 200 to
240 V, 7.5 to 11 kW and 3x 380 to 480 V, 18.5 to 22 kW
8I0CT100.000-1
Mains choke 3-phase 100 A, for ACOPOSinverter P84 3x 200
to 240 V, 15 kW and 3x 380 to 480 V, 30 to 55 kW
8I0CT184.000-1
Mains choke 3-phase 184 A, for ACOPOSinverter P84 3x 380
to 480 V, 75 to 90 kW
Table 21: 8I0CS025.000-1, 8I0CS045.000-1, 8I0CT004.000-1, 8I0CT010.000-1, 8I0C-
T016.000-1, 8I0CT030.000-1, 8I0CT060.000-1, 8I0CT100.000-1, 8I0CT184.000-1 - Order data
4.3.2 Technical data
Model number
8I0CS025.000-1
8I0CS045.000-1
General information
Certifications
CE
Yes
KC
Yes
Mains connection
Power dissipation
50 W
Inductance
2 mH
1 mH
Nominal current
25 A
45 A
Voltage drop
From 3 to 5% of the rated supply voltage. Higher values result in torque loss.
Operating conditions
Installation at elevations above sea level
0 to 1000 m
Protection
Choke
IP00
Terminals
IP20
Max. relative humidity
95%, non-condensing
No dripping water
Ambient temperature
0 to 45°C
Max. ambient temperature
Up to 55°C
1)
Maximum installation elevation
3000 m
2)
Environmental conditions
Temperature
Storage
-25 to 70°C
Mechanical characteristics
Weight
3.5 kg
General information
Conformity to standard
IEC 61800-5-1 (protection level 1 regarding overvoltages in the mains supply according to VDE 0160)
Table 22: 8I0CS025.000-1, 8I0CS045.000-1 - Technical data
1)
With current reduction of 2% per °C above 45°C.
2)
From 1000 to 3000 m, current reduced by 1% per 100 m
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...