Programming guidelines
226
ACOPOSinverter P84 User's Manual 2.10
2.8.11.11.4.1 Brake control logic expert parameters
Code
Name/Description
Factory settings
brH0
[BRH_b0]
0
Selection of the brake restart sequence if a run command is repeated while the brake is engaging.
0
[0]
(0)
: The brake engaging/brake release sequence is executed completely.
1
[1]
(1)
: The brake is immediately reopened.
Use in the open and closed-loop control
•
A run command may be requested during the brake release phase. Whether the sequence for the new brake engaging is executed,
depends on the value selected for
[BRH b0]
(brH0)
.
Movement command
Frequency
Relay or
Logic output
Frequency
bEn
Relay or
Logic output
[BRH_b0]
(brH0)
= 0
[BRH_b0]
(brH0)
= 1
Note:
If a run command is requested during the "ttr" phase, the complete brake control sequence is initialized.
brH1
[BRH b1]
0
Deactivation of the brake contact fault in the set mode.
0
[0]
(0)
: The "brake feedback" fault is active in steady state (fault if the contact is open during operation). The brake contact fault brF is monitored
in all operating phases.
1
[1]
(1)
: The "brake feedback" fault is not active in steady state. The brake contact error brF is only monitored during brake release and engaging
phases.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...