Programming guidelines
260
ACOPOSinverter P84 User's Manual 2.10
[CURRENT LIMIT] (CLI-)
Code
Name/Description
Setting range
Factory settings
CLI-
[CURRENT LIMIT.]
LC2
[Current limit 2]
[No]
(nO)
nO
[No]
(nO)
: Function not active
LI1
[LI1]
(LI1)
-
.
-
.
-
.
[...]
(...)
: See the assignment conditions
In state 0 of the input or the assigned bit, the first current limiting is active.
In state 1 of the input or the assigned bit, the second current limiting is active.
CL2
[2nd current limit]
1)
0 to 1.65 In
2)
1.5 In
2)
Second current limiting This parameter can be activated if
[2nd current limit]
(LC2)
is not equal to
[No]
(nO)
.
The adjustment range is limited to 1.36 In if
[Switch frequency]
(SFr)
is under 2 kHz.
Note:
If the setting is less than 0.25 In, the inverter can remain in error mode
[output phase loss]
(OPF)
, if this has been enabled,
"THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
. If it is below the no-load current of the
motor, the limitation has no effect.
Caution!
Make sure that the motor is designed to this current, since these are susceptible to a demagnetization.
Failure to follow this instruction can result in equipment damage.
CLI
[CURRENT LIMIT.]
1)
0 to 1.65 In
2)
1.5 In
2)
First current limiting.
The adjustment range is limited to 1.36 In if
[Switch frequency]
(SFr)
is under 2 kHz.
Note:
If the setting is less than 0.25 In, the inverter can remain in error mode
[output phase loss]
(OPF)
, if this has been enabled,
"THERM. MOTOR PROTECTION (tHt) and LOSS OF MOTOR PHASE (OPL)" on page 292
. If it is below the no-load current of the
motor, the limitation has no effect.
Caution!
Make sure that the motor is designed to this current, since these are susceptible to a demagnetization.
Failure to follow this instruction can result in equipment damage.
1)
This parameter can also be accessed via the
[SETTINGS]
(SEt-)
menu.
2)
In is the same as the rated current specified in the installation instructions and on the nameplate of the inverter.
Parameter that can be modified during operation or when stopped.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...