Programming guidelines
234
ACOPOSinverter P84 User's Manual 2.10
[HIGH SPEED HOISTING] (HSH-)
Code
Name/Description
Setting range
Factory settings
HSH-
[HIGH SPEED HOISTING]
Note:
This function cannot be used with certain other functions. Follow the instructions
see "APPLICATION FUNCT. FUn-" on page 197
HSO
[High speed hoisting optim]
[No]
(nO)
nO
[No]
(nO)
: Function not active
SSO
[F- reference]
(SSO)
: Mode "Frequency reference"
CSO
[Current limiting]
(CSO)
: Mode: "Current limiting"
COF
[Motor speed coeff.]
0 to 100%
100%
Frequency reduction coefficient calculated by the inverter for the lifting direction.
The parameter can be accessed if
[optim HSP hoist]
(HSO)
=
[F- reference]
(SSO)
.
COr
[Speed corr coeff]
0 to 100%
50%
Frequency reduction coefficient calculated by the inverter for descending direction.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is not equal to
[No]
(nO)
.
tOS
[Load Measurement time]
0.1 s to 65 s
0.5 s
Duration of frequency step for measurement.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is not equal to
[No]
(nO)
.
OSP
[Measurement spd]
0 to
[Rated motor fre-
quency]
(FrS)
40 Hz
Speed stabilized for measurement.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is not equal to
[No]
(nO)
.
CLO
[High speed I Limit]
0 to 1.65 In
1)
In
HSP limitation current.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is equal to
[Current limiting]
(CSO)
.
The adjustment range is limited to 1.36 In if
[Switch frequency]
(SFr)
is under 2 kHz.
Note:
If the setting is below 0.25 in, then there is a confirmation of the risk of locking with the fault
[output phase loss]
(OPF)
.
SCL
[Current limit]
0 to 599 Hz
40 Hz
Frequency threshold, above which the high-speed limitation current is active.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is equal to
[Current limiting]
(CSO)
.
rSd
[Rope slack config.]
[No]
(nO)
"Rope slack" function.
The parameter is accessible if
[optim HSP hoist]
(HSO)
is not equal to
[No]
(nO)
.
nO
[No]
(nO)
: Function not active.
drI
[Calc FU]
(drI)
: External load measurement by an estimate of the inverter torque.
PES
[ext. sensor]
(PES)
: External load measurement by measuring encoder; Assignment is only possible if
[ext. sensor]
(PES)
is not equal to
[No]
(nO)
.
rStL
[Rope slack trq level]
0 to 100%
0%
Adjustment threshold corresponding to a load weighing slightly less than the hook when off-load, as a % of the rated load.
The parameter is accessible when
[config. slack rope]
(rSd)
is assigned.
1)
In is the same as the rated current specified in the installation instructions and on the nameplate of the inverter.
Parameter that can be modified during operation or when stopped.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...