1.3.16 Connection diagram
1.3.16.1 Wiring diagram
Wiring diagram in accordance with standard EN 954-1 category 1 and IEC/EN 61508 SIL 1, stopping category 0
in accordance with standard IEC/EN 60204-1
Single-phase voltage supply (8I84T200075.01P-1 to 8I84T200750.01P-1)
Diagram with line contactor
Any existing
Braking resistor
Diagram with switch disconnecter
Any existing
Braking resistor
(1) Mains choke, if required (mandatory for inverters 8I84T200400.01P-1 to 8I84T200750.01P-1)
(2 ) Fault relay contacts, for remote signaling of inverter status
Information:
Lock the error that displays the loss of a line phase (IPL), to enable the operation of the models
8I84T200075.01P-1 to 8I84T200750.01P-1 in a single-phase network (see programming manual). If the
error is set to the factory values, the inverter remains locked in error mode.