Programming guidelines
ACOPOSinverter P84 User's Manual 2.10
257
[TORQUE CONTROL] (tOr-)
Code
Name/Description
Setting range
Factory settings
tOr-
[TORQUE CONTROL]
This function is only accessible if
[Type motor control]
(Ctt)
=
[SVC I]
(CUC)
or
[FVC]
(FUC)
.
Note:
This function cannot be used with certain other functions. Follow the instructions in
see "APPLICATION FUNCT. FUn-" on page 197
Note:
This function is not compatible with the fault management of
[load relax fault]
(AnF)
.
tSS
[Alt Torque / v]
[No]
(nO)
nO
[No]
(nO)
: Function not active. The other parameters are then not accessible.
YES
[Yes]
(YES)
: Permanent torque limitation
LI1
[LI1]
(LI1)
-
.
-
.
-
.
[...]
(...)
: See the assignment conditions
In state 1 of the input or of the associated bit: Torque control
In state 0 of the input or of the associated bit: Speed control
tr1
[Ref. Torq.]
[No]
(nO)
nO
[No]
(nO)
: Not assigned (Zero torque reference).
AI1
[AI1]
(AI1)
: Analog input
AI2
[AI2]
(AI2)
: Analog input
LCC
[HMI]
(LCC)
: Graphics terminal
Mdb
[Modbus]
(Mdb)
: Not applicable
CAn
[CANopen]
(CAn)
: Integrated communication interface (POWERLINK)
nEt
[Com. Card]
(nEt)
: Communication card (if present)
PG
[Encoder]
(PG)
: Encoder input if encoder card has been inserted
100% of the reference corresponds to 300% of the rated torque.
tSd
[Pref. Torque]
[No]
(nO)
nO
[No]
(nO)
: Function not active
LI1
[LI1]
(LI1)
-
.
-
.
-
.
[...]
(...)
: See the assignment conditions
With state 0 of the assigned input or bit, the prefix of the torque corresponds to the that of the reference.
With state 1 of the assigned input or bit, the torque has the opposite prefix to that of the reference.
trt
[Torque coeff]
0 to 1000%
100%
Coefficient applied to
[Ref. torque]
(tr1)
trP
[Time torque ramp]
0 to 99.99 s
3 s
Rise and fall times for a variation of 100% of the rated torque.
tSt
[Type Stop M Contr.]
[Speed.]
(SPd)
SPd
[speed]
(SPd)
: Speed control stop according to the normal stop configuration (
see "STOP MODE (Stt-)" on page 206
)
YES
[freewheel stop]
(YES)
: Freewheel stop
SPn
[M at 0]
(SPn)
: Zero torque stop, magnetization in the motor is maintained, however. This type of function is only possible if
[Motor control type]
(Ctt)
=
[FVC]
(FUC)
.
SPt
[time stop magmot]
0 to 3600 s
1
The parameter is accessible if
[Type Stop M Contr.]
(tSt)
=
[M at 0]
(SPn)
.
Rotation time after a stop, important for fast restart.
dbp
[M. ctrl. pos bandw.]
0 to 2x
[Max. output freq.]
(tFr)
10 Hz
Positive deadband.
Value added algebraically to the frequency reference.
Example for
dbp
= 10:
•
If reference = 50 Hz: 50 + 10 = 60
•
If reference = -50 Hz: - 50 + 10 = - 40
dbn
[M. ctrl. neg. bandw.]
0 to 2x
[Max. output freq.]
(tFr)
10 Hz
Negative deadband.
Value subtracted algebraically from the frequency reference.
Example for
dbn
= 10:
•
If reference = 50 Hz: 50 - 10 = 40
•
If reference = -50 Hz: - 50 - 10 = - 60
rtO
[M ctrl timeout]
0 to 999.9 s
60
Period of time after the automatic stop of the torque-controlled mode in the event of a fault or alarm.
tOb
[M ctrl mgt]
[Alarm]
(ALrM)
Response of the inverter after the expiry of the time
[M ctrl Timeout]
(rtO)
.
ALrM
[Alarm]
(ALrM)
FLt
[Fault]
(FLt)
: Fault when stopping in freewheel stop.
Parameter that can be modified during operation or when stopped.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...