Programming guidelines
202
ACOPOSinverter P84 User's Manual 2.10
2.8.11.6 Summing input / Subtracting input / Multiplier
Fr1 or Fr1b
SA2
SA3
dA2
dA3
MA2
MA3
A
A = (
Fr1
or
Fr1b
+
SA2
+
SA3
-
dA2
-
dA3
) x
MA2
x
MA3
•
If
SA2
,
SA3
,
dA2
,
dA3
are not used, they are set to 0.
•
If MA2,
MA3
are not used, they are set to 1.
•
A is limited by parameters "Low speed"
LSP
and "High speed"
HSP
.
•
In the multiplication the signal at
MA2
or
MA3
in % is captured. 100% corresponds to the maximum value of
the corresponding input. If
MA2
or
MA3
are sent by the communication bus or the graphic display terminal,
a multiplication variable
MFr
see "With graphics terminal: Internal inverter states and values" on page 136
must be sent via the bus or the graphic display terminal.
•
The inversion of the direction of rotation in the case of a negative result can be locked (