Programming guidelines
272
ACOPOSinverter P84 User's Manual 2.10
2.8.11.24 Switching motors/configuration [MULTIMOT/CONFIGURATION]
The inverter can contain up to 3 configurations that can be saved via the
[FACTORY SETTING]
(FCS-)
menu.
Each of these configurations can be activated remotely, enabling adaptation to:
•
2 or 3 different motors or mechanisms (multimotor mode)
•
2 or 3 different configurations for a single motor (multiconfiguration mode)
The two switching modes cannot be combined.
Note:
The following conditions MUST be observed:
•
Switching may only take place when stopped (inverter locked). If a switching request is sent
during operation, it will not be executed until the next stop.
•
In the event of motor switching, the following additional conditions apply:
– When the motors are switched, the power and control terminals concerned must also
be switched as appropriate.
– The maximum power of the inverter must not be exceeded by any of the motors.
•
All the configurations to be switched must be set and saved in advance in the same hardware
configuration, this being the definitive configuration (option and communication cards). In the
event of non-compliance with this provision, there is the danger that the inverter will be locked
with the fault
[incorrect config.]
(CFF)
.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...