Programming guidelines
176
ACOPOSinverter P84 User's Manual 2.10
The encoder configuration can also be accessed in the menu
[DRIVE DATA]
(drC-)
.
[CONFIG. ENCODER] (IEn-)
Code
Name/Description
Setting range
Factory settings
IEn-
[ENCODER CONFIG]
The encoder parameters can only be enabled if the encoder card has been inserted and the available selection options depend on the type of
encoder card.
EnS
[Encoder type]
[AABB]
(AAbb)
These parameters can only be accessed if an incremental encoder card has been inserted.
To be configured according to the encoder type used.
AAbb
[AABB]
(AAbb)
: For the signals A, A-, B, B-.
Ab
[AB]
(Ab)
: For the signals A, B
A
[A]
(A)
: For the signal A. The value is not accessible if
[Encoder active]
(EnU)
=
[Control]
(rEG).
EnC
[Encoder]
[Not done]
(nO)
Checks the encoder feedback (
see "Encoder testing" on page 157
)
This parameter can be accessed when an encoder card has been inserted and if
[Encoder active]
(EnU)
is not
[Dig reference]
(PGr)
.
nO
[Not done]
(nO)
: Test not performed.
YES
[Yes]
(YES)
: Activates monitoring of the encoder.
dOnE
[done]
(dOnE)
: Test performed successfully.
The test procedure is used to check the following:
•
The direction of rotation of the encoder / motor
•
Existing signals (continuity of wiring)
•
Number of pulses/rotations
If a fault is detected, the inverter is locked in fault mode
[Encoder fault]
(EnF)
.
EnU
[Encoder active]
[No]
(nO)
The parameter is accessible if an encoder card is present .
nO
[No]
(nO)
: Function not active. In this case, access to the other parameters is not possible.
SEC
[Security]
(SEC)
: The encoder is only for the monitoring as a speed feedback.
rEG
[Control]
(rEG)
: The encoder indicates the actual speed value for control and monitoring purposes. This configuration is performed automatically
if the inverter is configured to run with closed control loop (
[Motor control type]
(Ctt)
=
[FVC]
(FUC)
. If
[motor control type]
(Ctt)
=
[SVC U]
(UUC)
, then the encoder runs in speed feedback mode and allows the static correction of the speed. This configuration is not available for other
values of
[Motor control type]
(Ctt)
.
PGr
[Reference]
(PGr)
: The encoder provides a reference. Can only be selected with an incremental encoder card.
PGI
[Number of pulses]
100 to 5000
1024
Number of pulses per encoder revolution.
These parameters can only be accessed if an incremental encoder card has been inserted.
PGA
[Reference type]
[Encoder]
(EnC)
The parameter is accessible if
[Encoder active]
(EnU)
=
[reference]
(PGr)
.
EnC
[Encoder]
(EnC)
: Use of an encoder.
PtG
[Freq. Gene.]
(PtG)
: Use of a frequency generator (reference value without sign).
EIL
[Min. freq. value]
-300 to 300 kHz
0
The parameter is accessible if
[Encoder active]
(EnU)
=
[reference]
(PGr)
and if
[Reference type]
(PGA)
=
[Freq. Gene.]
(PtG)
.
The frequency is equal to the minimum speed.
EFr
[Max. freq. value]
0 to 300 kHz
300 kHz
The parameter is accessible if
[Encoder active]
(EnU)
=
[reference]
(PGr)
and if
[Reference type]
(PGA)
=
[Freq. Gene.]
(PtG)
.
The frequency is equal to the maximum speed.
EFI
[Filter Freq. Signal]
0 to 1000 ms
0
The parameter is accessible if
[Encoder active]
(EnU)
=
[reference]
(PGr)
.
Filtering of any faults.
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...