1
General Information
1.1
Revision History
Rev.
Date
Editor
Changes
N
2021-09
Lu
NEW Software Revision Release 2.12-1 or higher
Corrections/Repairs
• J1939 Volvo EMS proprietary J1939 data: If “15102 Device type” is configured to
•
“EMS2 Volvo”, the J1939 proprietary values (page “J1939 Special”) are not
indicated and not passed to the corresponding LogicsManager variables (03.73 to
03.85) and AnalogManager variables (09.19 to 09.23).
Remote control values (like start/stop speed biasing etc.) are transmitted correctly.
For this reason the engine could be controlled but no proprietary J1939 data are
available in the easYgen.
• Scania S8 proprietary J1939 data: If “15102 Device type” is configured to “S8
•
Scania”, the J1939 proprietary values (page “J1939 Special”) are not indicated and
not passed to the corresponding LogicsManager variables (14.22 to 14.35) and
AnalogManager variables (09.26 to 09.29).
Remote control values (like start/stop speed biasing etc.) are transmitted correctly.
For this reason the engine could be controlled but no proprietary J1939 data are
available in the easYgen.
• J1939 failure codes DM1 and DM2 ToolKit: The J1939 failure codes DM1 and DM2
•
are not visible in ToolKit if “15102 Device type” is configured to the following
devices: "Standard C", "S8 Scania", "ECU8/9 MTU" or "Hatz EDC7".
• DM1 alarms of SPN 3719, 3720 DM1: Alarms of SPNs “3719 DPF 1 Soot load” and
•
“3720 DPF 1 Ash load” are not indicated in the alarm list.
M
2021-06
LU
NEW Software Revision Release 2.12-0 or higher
NEW features & functions
• Configuration: The parameter "Parameter update rate" is now accessible in ToolKit
•
(refer to
).
• AVR setpoint via standard J1939 message prepared (refer to
).
•
• Introduction of a new J1939 device type "Standard C" for ECUs which require
•
counter and message checksum for TSC1 (refer to
).
• Scania S8: Support of proprietary exhaust gas aftertreatment related J1939
•
messages (refer to
╚═▷ “Special Scania S8 messages”
• Support of battery charger related J1939 messages (SPNs: 4990 to 4993).
•
• The setpoint indication on display is made more comfortable in regards of the
•
source information.
• Communication Ports
•
◦ The communication timeout limit for CAN load share and control messages is
◦
now configurable (refer to
).
◦ The communication timeout "7489 Timeout cycles" limit for Ethernet load
◦
share and control messages is now configurable with code level 2 instead of
12.
◦ New load share message timeout flags available for the event logger and as
◦
LogicsManager command variables 08.78 and 08.80 (refer to
).
Corrections/Repairs
• Code level changed
•
◦ Code level of parameter "10419 REBOOT" changed from 4 to 2.
◦
◦ Code level of parameter "3228 Enabled changed from 4 to 2.
◦
◦ Code level of parameter "3203 Enabled" changed from 4 to 2.
◦
• J1939: PGN 57344 Cab Message 1 CM1 (with SPNs 3695, 3696) now with flexible
•
destination address.
• The AnalogManager variable "05.88 Manual P setp. [kW]" is now presented in kW.
•
25
easYgen-3000XT Series
B37574
1 General Information
1.1 Revision History
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...