• If the mains return during an emergency power operation (GCB is closed), the mains
•
settling time (parameter
) must expire before the load is transferred from
the generator to mains operation.
Activation of emergency power
If the mains are not within the configured frequency and voltage operating limits (
“4.5.3.3 Mains Operating Ranges”
) for at least the time configured in the parameter
"Mains fail delay time" (parameter
), an emergency power operation is
activated.
MCB malfunction
An emergency power operation will be performed, if the control is not able to close or
recluse the MCB and the alarm "Fail to close MCB" occurs.
Mains rotation field alarm
If the mains returns after a mains failure with a reversed rotation direction the generator
remains in emergency power operation until the mains rotation matches the rotation of
the generator set.
The generator will not start upon a mains rotation field alarm, but it will keep on running
if it has already started.
The following parameters only apply to application mode
A04
.
ID
Parameter
CL
Setting range
[Default]
Description
2802
Emergency run
2
[On]
If the unit is in the AUTOMATIC
operating mode and a mains fault
occurs according to the following
parameters, the engine is started
and an automatic emergency
operation is carried out.
Off
No emergency operation is carried
out.
2800
Mains fail delay time
(Mains failure start
delay)
2
0.00 to 99.99 s
[3.00 s]
To start the engine and to carry
out an emergency operation the
monitored mains must be failed
continuously for the minimum
period of time set with this
parameter.
Notes
This delay time starts only if the
easYgen is in AUTOMATIC
operating mode and emergency
power is activated.
418
easYgen-3000XT Series
B37574
4 Configuration
4.4.6 Emergency Run
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...