ID
Parameter
CL
Setting range
[Default]
Description
The MCB can be synchronized with
an individual slip frequency (also
negative).
The activation of MCB sync. with
separate slip can be selected with
parameter
configuration | breakers | MCB)
hat comes with the MCB slip freq.
setpoint offset parameter
(HMI: configuration |
application | controller |
frequency).
5505
Phase matching gain
2
1 to 99
[5]
The phase matching gain
multiplies the setting of the
proportional gain (parameter
) for phase matching control.
5506
Phase matching df-
start
2
0.02 to 0.25 Hz
[0.05 Hz]
Phase matching will only be
enabled if the frequency
difference between the systems to
be synchronized is below the
configured value.
12918
Setpoint 2 freq.
(Setpoint 2 frequency)
2
Determined by LogicsManager
86.81
[(0 & 1) & 1]
If this LogicsManager condition is
TRUE, the frequency setpoint 2
will be used instead of frequency
setpoint 1. The frequency (result
of AM)
will be taken into account.
Notes
For information on the
LogicsManager and its default
settings see
.
Remotely switching the setpoint is
possible: Use the LogicsManager
command variable for input that is
correlating with the dedicated bit
of parameter
5516
Start frequency
control level
1
15.00 to 85.00 Hz
[47.00 Hz]
The frequency controller is
activated when the monitored
generator frequency has
exceeded the value configured in
this parameter.
This prevents the easYgen from
attempting to control the
frequency while the engine is
completing its start sequence.
5517
Start frequency
control delay
1
0 to 999 s
[5 s]
The frequency controller is
enabled after the configured time
for this parameter expires.
5503
Freq. control setpoint
ramp
(Frequency control
setpoint ramp)
2
0.10 to 60.00 Hz/s
[2.50 Hz/s]
The different setpoint values are
supplied to the controller via this
ramp.
The slope of the ramp is used to
alter the rate at which the
controller modifies the setpoint
value.
348
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.4 Frequency Control