Example 2: Stop Request
Fig. 284:
Modbus - write register - stop request
By double-clicking the address, a Write Register command may be issued.
shows how bit 1 is set using the ModScan32 Software.
Example 3: External Acknowledge
Fig. 285:
Modbus - write register - external acknowledge
By double-clicking the address, a Write Register command may be issued.
shows how bit 4 is set using the ModScan32 Software.
Example 4: Shutdown Command
Fig. 286:
Modbus - write register - shutdown command
By double-clicking the address, a Write Register command may be issued.
shows how bit 9 is set using the ModScan32 Software.
Sample for Free alarm 1
This (remote) shutdown request can be taken by LogicsManager equation 12230 to set
Flag 1 (see
). To perform an immediately shutdown, the free alarm has to be
configured as alarm Class F. Free alarm 1 configuration
Monitoring source LM
»Free alarm 1« is set to Flag 1 and the Alarm class 8121
is set to Class F.
793
easYgen-3000XT Series
B37574
6 Application Field
6.5.1.1 Remote Start/Stop, Shutdown, And Acknowledgment
Released