ID
Parameter
CL
Setting range
[Default]
Description
If the battery voltage exceeds the
threshold (plus the hysteresis)
again before the delay expires the
time will be reset.
3501
3507
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
3502
3508
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
3503
3509
Enabled
2
4
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.6.15 Monitoring PV load reference
General notes
The PV load reference function contains a monitor for generator reverse power. It is
enabled if parameter
) is configured to ”Regulated“. The monitor observes the
system generator load and trips the alarm ”08.71 PV disconnect“ if the real generator
load underruns the configured disconnect level e.g. in case of reverse power. Then the PV
power can be cut. This can be maintained if the LogicsManager "08.71 PV disconnect" is
assigned to a relay output.
576
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.15 Monitoring PV load reference
Released