Function
The reactive power controller PID is always receiving a reactive power setpoint even the
setpoint is entered as power factor or as power factor setpoint. The PT1 filter behavior is
always included (Refer to drawing) but the filter can configured so that it has no
influence.
Fig. 164:
Setpoint Jump (standardized with height 1) and the resulting PT1 setpoint
Four reactive power setpoint filters are placed in the easYgen in regards to:
• Gen PF setpoint setting
•
• Reactive power characteristic Q(V)
•
• Reactive power characteristic Q(P)
•
• Reactive power characteristic Q(V) limit
•
316
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.2.4 Reactive Power / Power Factor setpoint filter
Released