Simple (function)
Extended (configuration)
Result
In application mode
A03
to
A13
"Command: close GCB"
Deactivated by default
[99.07] Relay 7 [R07] - Mains
decoupling / freely configurable /
Command: open GCB
dependent
on
application
mode and
Logics
Command
Variable
[07.25]
In application mode
A01
pre-configured to
mains decoupling. Relay energizes if the
internal condition "Mains decoupling" is
TRUE to decouple the genset from the
mains.
In application mode
A02
to
A13
"Command: open GCB"
Deactivated by default
[99.08] Relay 8 [R08] - Free /
Command: close MCB
FALSE
In application mode
A01
,
A02
,
A03
,
A05
,
A07
,
A08
,
A09
,
A10
and
A11
to
A13
freely configurable relay (unassigned)
In application mode
A04
and
A06
"Command: close MCB"
Deactivated by default
[99.09] Relay 9 [R09] - Mains
decoupling / freely configurable /
Command: open MCB
dependent
on
application
mode and
Logics
Command
Variable
[07.25]
In application mode
A01
,
A02
,
A03
,
A05
,
A07
,
A08
,
A09
,
A10
and
A11
to
A13
pre-
configured to mains decoupling. Relay
energizes if the internal condition "Mains
decoupling" is TRUE to decouple the genset
from the mains.
In application mode
A04
and
A06
"Command: open MCB"
Deactivated by default
[99.10] Relay 10 [R10] - Auxiliary
services / freely configurable
dependent
on Logics
Command
Variable
[03.01]
In application mode
A01
,
A02
,
A03
,
A04
,
A07
,
A08
,
A10
and
A11
to
A13
pre-
configured to auxiliary services. Relay
energizes if the internal condition "Aux.
services" is TRUE to activate the auxiliary
services (it energizes prior to an engine
start and de-energizes with the engine
stop)
In application mode
A05
,
A06
and
A09
"Command: close GGB"
1136
easYgen-3000XT Series
B37574
9 Appendix
9.3.5 Factory Settings