The normal operation monitoring limits will be enabled again, if one of the following
conditions is fulfilled:
• Idle mode has ended and generator frequency has reached rated frequency -1 Hz.
•
(e.g. 49 Hz at 50 Hz rated)
• Idle mode has ended and engine delayed monitoring (parameter
) has
•
expired.
The flexible limits 33 through 40 are disabled during idle mode operation (
).
ID
Parameter
CL
Setting range
[Default]
Description
12570
Auto idle mode
2
Determined by LogicsManager
86.20
[(0 & 1) ≥1 0]
= 15719
Once the conditions of the
LogicsManager have been fulfilled
the engine will be operated in idle
mode automatically for the
configured time during start-up.
Monitoring is limited as described
above.
This function may always be
configured to "1" for example.
Notes
For information on the
LogicsManager and its default
settings see
.
12550
Constant idle run
(Continuous idle mode)
2
Determined by LogicsManager
86.14
[(0 & 1) & 0]
= 10713
As long as the conditions of the
LogicsManager have been fulfilled
the engine will be continuously
operated in idle mode. Monitoring
is limited as described above. A
key switch via a DI may be
configured here for example.
Notes
The idle mode is blocked if the
GCB is already closed.
For information on the
LogicsManager and its default
settings see
.
3328
Automatic idle time
(Time for automatic idle
mode)
2
1 to 9999 s
[30 s]
The automatic idle mode is active
for the time configured here.
Monitoring is limited as described
above during this time.
3329
During emergency /
critical
(Idle mode possible
during emergency /
critical operation)
2
Yes
If an emergency or critical
operation is enabled, the engine
will go to rated speed only after
completing the configured idle
mode.
[No]
If an emergency or critical
operation is enabled, no idle run
227
easYgen-3000XT Series
B37574
4 Configuration
4.4.1.4 Idle Mode
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...