ID
Parameter
CL
Setting range
[Default]
Description
87.70LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:96.{xx}LM:
Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE. Example: 96.01 LM: Flag 1,
96.02 LM: Flag 2, ..., 96.32 LM:
Flag 32
4.5.4.3
Synchronization GCB
General notes
NOTICE!
If load-dependent start/stop (refer to
╚═▷ “4.4.5.5 Load Dependent Start/Stop (LDSS)”
) is
enabled, this monitoring function must be configured with a shutdown alarm class C, D,
E, or F) or disable load-dependent start/stop if triggered to ensure that the next engine
will be started.
ID
Parameter
CL
Setting range
[Default]
Description
3060
Monitoring
2
[On]
Monitoring of the GCB
synchronization is carried out
according to the following
parameters.
Off
Monitoring is disabled.
3063
Delay
2
3 to 999 s
[60 s]
If it was not possible to
synchronize the GCB within the
time configured here, an alarm
will be issued.
The message "GCB syn. timeout"
is issued and the logical command
variable "08.30" will be enabled.
3061
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
3062
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
542
easYgen-3000XT Series
B37574
4 Configuration
4.5.4.3 Synchronization GCB
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...