ID
Parameter
CL
Setting range
[Default]
Description
Period of use
The »period of use hours« (value
of ID 2580) are considered when
evaluating the engines to be
started for gensets with same
priority. The gensets are utilized in
a way that the period of use hours
are equalized over time for all
participating gensets. The genset
with the lowest period of use
hours will be started first.
5756
Changes of engines
2
Load dependent start stop:
Changes of engine
With setting "Off" no time slot is
considered and the change of
engine is related directly on the
passed engine hours. With a
configured time slot (32/64/128 h)
a minimum of passed engine
running hours is taken into
account before changing the
gensets.
If LDSS is configured to act on
best possible equal maintenance
hours or "period of use" hours, the
change of engines can be
determined by given time slots.
The LDSS therefore creates an
individual unit’s time group for
each engine. Refer to manual
chapter »Engine time groups« for
more details.
Notes
If the LDSS function »Fit service
hours« (parameter
) is
enabled with "Equal" or "Period of
use" hours, this configuration gets
valid. Otherwise this parameter
can be ignored.
For more details go to chapter
“9.4.2.10 Group 11: Engine
values”
[Off]
No engine change will be
performed. The engines are
selected according to the setting
of parameter
(Fit
service hours) with 1 hour spacing
in case of load changes.
All 32h
All 64h
All 128h
All relevant engines are changed
with a 32/64/128 hour spacing.
Example 1
• "Changes of engines" is
•
configured to "All 64h"
• Generator 1 has 262
•
maintenance hours
remaining
• Generator 2 has 298
•
maintenance hours
remaining
401
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.3 Generator Selection
Released
Содержание easYgen-3000XT Series
Страница 109: ...Fig 72 easYgen 3100XT P1 Series 109 easYgen 3000XT Series B37574 3 Installation 3 4 1 Interfaces overview Released...
Страница 122: ...Fig 85 Menu structure menu tree easYgen 3100XT P1 3200XT P1 122 easYgen 3000XT Series B37574 4 Configuration Released...
Страница 332: ...Fig 169 Load sharing diagram 332 easYgen 3000XT Series B37574 4 Configuration 4 4 4 3 6 Load Sharing Released...